SECTION 11208
METERING MANHOLES
NOTE ** Warminster Fiberglass Co. metering manholes.
NOTE **
NOTE ** This section is based on products manufactured by
Warminster Fiberglass Co., which is located at the
following address:
NOTE ** P.O. Box 188
NOTE ** Southampton PA 18966-0188
NOTE ** Tel: (215) 953-1260
NOTE ** Fax: (215) 357-7893
NOTE **
NOTE ** Warminster Fiberglass Co. has manufacturing
facilities in Southampton PA and in Jacksonville
TX, and manufactures a wide line of fiberglass
reinforced polyester resin products for the water
and waste treatment industry, including instrument
consoles, Palmer-Bowlus flumes, Parshall flumes,
slide gates, wash troughs, effluent troughs, finger
weirs, weir plates, scum baffles, metering
manholes, density current baffles, and odor control
systems.
NOTE **
NOTE ** Warminster also manufactures fiberglass doors and
frames and buildings, shelters, and enclosures for
a wide range of uses.
NOTE **
NOTE ** SECTION 11208 - METERING MANHOLES, Copyright 1997,
The Architect's Catalog, Inc.
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Metering manholes.
1.2 RELATED SECTIONS
NOTE ** Delete any sections below not relevant to this
project; add others as required.
A. Section 03300 - Cast-In-Place Concrete.
B. Section 08342 - Fiberglass Doors and Frames.
C. Section 11201 - Wash Troughs.
D. Section 11202 - Effluent (Collection) Troughs (Launders).
E. Section 11203 - Finger Weir Pans.
F. Section 11204 - Weir Plates, Scum Baffles, and Brackets.
G. Section 11205 - Density Current Baffle System.
H. Section 11206 - Palmer-Bowlus Flumes.
I. Section 11207 - Parshall Flumes.
J. Section 11286 - Slide Gates and Guides.
K. Section 11305 - Odor Control System.
L. Section 13122 - Pre-Engineered Fiberglass Buildings.
M. Section 13411 - Instrument Consoles.
1.3 REFERENCES
NOTE ** Delete references from the list below that are not
actually required by the text of the edited
section.
A. ANSI/AWWA F101 - Contact Molded, Fiberglass-Reinforced
Plastic Wash Water Troughs and Launders; American Water
Works Association.
B. ASTM D 256 - Standard Test Methods for Determining the
Pendulum Impact Resistance of Notched Specimens of
Plastics.
C. ASTM D 618 - Standard Practice for Conditioning Plastics
and Electrical Insulating Materials for Testing.
D. ASTM D 638 - Standard Test Method for Tensile Properties
of Plastics.
E. ASTM D 696 - Standard Test Method for Coefficient of
Linear Thermal Expansion of Plastics Between -30 degrees
C and 30 degrees C.
F. ASTM D 790 - Standard Test Methods for Flexural
Properties of Unreinforced and Reinforced Plastics and
Electrical Insulating Materials.
G. ASTM D 2583 - Test Method for Indentation Hardness of
Rigid Plastics by Means of a Barcol Impressor.
H. ASTM D 3753 - Standard Specification for Glass-Fiber-
Reinforced Polyester Manholes.
1.4 SUBMITTALS
A. Submit under provisions of Section 01300.
B. Product Data: Test results of fiberglass reinforced
plastic laminate.
C. Shop Drawings: Show:
1. Critical dimensions, jointing and connections,
fasteners and anchors.
2. Materials of construction.
3. Sizes, spacing, and locations of structural members,
connections, attachments, openings, fasteners, and
loads.
D. Samples: 8-inch square sample of fiberglass reinforced
plastic laminate.
E. Manufacturer's installation instructions.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Store products indoors and protect from construction
traffic and damage.
PART 2 PRODUCTS
2.1 MANUFACTURER
A. Provide products manufactured by Warminster Fiberglass
Company; P.O Box 188, Southampton PA 18966-0188; ASD.
Tel. (215) 953-1260, Fax. (215) 357-7893.
NOTE ** Delete one of the two following paragraphs;
coordinate with Division 1 requirements.
B. Requests for substitution will be considered in
accordance with provisions of Section 01600.
C. Substitutions: Not permitted.
2.2 METERING MANHOLES
A. Fiberglass Laminate:
1. Tensile strength (ASTM D 638): 14,000 psi.
2. Flexural strength (ASTM D 790): 25,000 psi.
3. Flexural modulus (ASTM D 790): 1,000,000 psi.
4. Impact, notched, Izod (ASTM D 256): 15 ft-lb/in.
5. Barcol hardness (resin-rich surface) (ASTM D 2583):
40 minimum, average.
6. Coefficient of thermal expansion, average (ASTM D
696): 0.000105 in/in/degree F.
7. Test coupons prepared in accordance with ASTM D 618.
NOTE ** Delete the following paragraph if not required.
8. Chemical resistance: Comply with ANSI/AWWA F101,
Type II classification.
B. Construction: Fiberglass reinforced plastic, complying
with ASTM D 3753; factory-assembled, ready for
installation except for field-installed equipment.
1. Interior surface smooth and resin rich; free of pits,
porosity, cracks, crazing, and dry glass.
2. Exterior laminate: 1/2 inch thick, minimum,
consisting of polyester resin with 25 percent minimum
glass content.
3. Cover: 1/4 inch thick fiberglass, hinged one side,
with hasp for locking; provide soft neoprene sponge
gasket for sealing.
4. Inlet and outlet pipes: Integrally molded to manhole
with laminates on both the interior and exterior
surfaces; inlet and outlet boots with stainless steel
straps to diameter of inlet and outlet pipe.
5. Access ladder: Fiberglass; bolted to manhole wall.
6. Mounting flange: 4 inch, integrally molded around
circumference of manhole for anchoring to concrete
pad.
7. Gasket: 1/2 inch thick neoprene sponge pad.
NOTE ** Delete all but one of the following size
descriptions, unless more than one size is
required. In that case, indicate sizes on the
drawings.
8. Size: 48 inch diameter, with 51 inch diameter cover.
9. Size: Reduced manway, 21 inch diameter opening.
10. Size: Reduced manway, 24 inch diameter opening.
11. Size: As indicated on drawings.
12. Height: As indicated on drawings.
C. Flume Assemblies: Laminate flumes into manholes to form
a totally watertight assembly.
1. For flumes longer than manhole diameter, cover flume
with fiberglass plate of sufficient strength
laminated to make watertight seal and to withstand
loads when backfilled.
NOTE ** Plamer-Bowlus flumes will be from 4 inches to 24
inches.
NOTE ** Parshall flumes will be from 2 inches to 24 inches.
2. Flume sizes: As indicated on drawings.
NOTE ** Delete any of the optional accessories, below, that
are not required.
D. Accessories:
1. Anchor bolts: Type 304 stainless steel.
2. Full open, hinged cover with locking latch.
3. Staff gauge graduated in 50 divisions per foot
mounted inside flume.
4. Staff gauge graduated in inches mounted inside flume.
5. Stilling well, 10 inches diameter.
6. Bubbler tube.
7. Tracks for probes, molded in.
8. Bushing for ultrasonic transponder mounting.
9. Bulkhead fittings.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that dimensions are correct and project conditions
are suitable for installation. Do not proceed with
installation until unsatisfactory conditions have been
corrected.
3.2 INSTALLATION
A. Install products in accordance with manufacturer's
instructions.
B. Ensure that products are installed plumb and true, free
of warp or twist, within tolerances specified by the
manufacturer and as indicated in the contract documents.
C. Verify that concrete slab is level and smooth trowelled.
Level with grout if necessary. Ensure that piping is
self supported by bedding.
D. Handle manhole using slings of nylon or similar fabric.
Do not drop or impact.
E. Place sponge pad on concrete slab. Drill holes in
accordance with template for stainless steel anchor
bolts.
F. Lower manhole onto pad and install anchor bolts.
G. Check level of flume in both planes, and adjust as
required.
H. Connect piping. Do not lubricate neoprene boots. Secure
with stainless steel clamp.
I. Backfill with pea gravel, 1/4 inch to 3/4 inch diameter,
specified in Division 2, using uniform lifts not
exceeding 12 inches.
J. Where cut holes are required, seal as directed by the
Engineer.
3.3 ADJUST AND CLEAN
A. Clean surfaces in accordance with manufacturer's
instructions.
B. Remove trash and debris, and leave the site in a clean
condition.
END OF SECTION